Temperature

Eaton.UPS.Monitoring.Eaton.Monitoring.Environment.Temperature (UnitMonitor)

Description for the new unit monitor.

Element properties:

TargetEaton.UPS.Device
Parent MonitorSystem.Health.AvailabilityState
CategoryCustom
EnabledTrue
Alert GenerateTrue
Alert SeverityWarning
Alert PriorityHigh
Alert Auto ResolveTrue
Monitor TypeSystem.NetworkManagement.SnmpTrapProvider.2SingleEvent2StateMonitorType
RemotableTrue
AccessibilityInternal
Alert Message
Temperature
Description: {0}
RunAsDefault

Source Code:

<UnitMonitor ID="Eaton.UPS.Monitoring.Eaton.Monitoring.Environment.Temperature" Accessibility="Internal" Enabled="true" Target="EUD!Eaton.UPS.Device" ParentMonitorID="Health!System.Health.AvailabilityState" Remotable="true" Priority="Normal" TypeID="NetworkLibrary!System.NetworkManagement.SnmpTrapProvider.2SingleEvent2StateMonitorType" ConfirmDelivery="false">
<Category>Custom</Category>
<AlertSettings AlertMessage="Eaton.UPS.Monitoring.Eaton.Monitoring.Environment.Temperature.AlertMessage">
<AlertOnState>Warning</AlertOnState>
<AutoResolve>true</AutoResolve>
<AlertPriority>High</AlertPriority>
<AlertSeverity>Warning</AlertSeverity>
<AlertParameters>
<AlertParameter1>$Data/Context/SnmpVarBinds/SnmpVarBind[5]/Value$</AlertParameter1>
</AlertParameters>
</AlertSettings>
<OperationalStates>
<OperationalState ID="FirstEventRaised" MonitorTypeStateID="FirstEventRaised" HealthState="Warning"/>
<OperationalState ID="SecondEventRaised" MonitorTypeStateID="SecondEventRaised" HealthState="Success"/>
</OperationalStates>
<Configuration>
<FirstIP>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPAddress$</FirstIP>
<FirstVersion>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPVersion$</FirstVersion>
<FirstOIDProps/>
<FirstExpression>
<Or>
<Expression>
<SimpleExpression>
<ValueExpression>
<XPathQuery Type="String">/DataItem/SnmpVarBinds/SnmpVarBind[4]/Value</XPathQuery>
</ValueExpression>
<Operator>Equal</Operator>
<ValueExpression>
<Value Type="String">.1.3.6.1.4.1.534.1.7.42</Value>
</ValueExpression>
</SimpleExpression>
</Expression>
<Expression>
<SimpleExpression>
<ValueExpression>
<XPathQuery Type="String">/DataItem/SnmpVarBinds/SnmpVarBind[4]/Value</XPathQuery>
</ValueExpression>
<Operator>Equal</Operator>
<ValueExpression>
<Value Type="String">.1.3.6.1.4.1.534.1.7.29</Value>
</ValueExpression>
</SimpleExpression>
</Expression>
<Expression>
<SimpleExpression>
<ValueExpression>
<XPathQuery Type="String">/DataItem/SnmpVarBinds/SnmpVarBind[4]/Value</XPathQuery>
</ValueExpression>
<Operator>Equal</Operator>
<ValueExpression>
<Value Type="String">.1.3.6.1.4.1.534.1.7.31</Value>
</ValueExpression>
</SimpleExpression>
</Expression>
</Or>
</FirstExpression>
<SecondIP>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPAddress$</SecondIP>
<SecondVersion>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPVersion$</SecondVersion>
<SecondOIDProps/>
<SecondExpression>
<SimpleExpression>
<ValueExpression>
<XPathQuery Type="String">/DataItem/SnmpVarBinds/SnmpVarBind[4]/Value</XPathQuery>
</ValueExpression>
<Operator>Equal</Operator>
<ValueExpression>
<Value Type="String">.1.3.6.1.4.1.534.1.7.40</Value>
</ValueExpression>
</SimpleExpression>
</SecondExpression>
</Configuration>