upsAdvOutputCurrent

MomUIGeneratedRule5afcd98df6554058b3190d8862338e2c (Rule)

Date: 2012-03-21
Author: Justin Bennett
Web: http://justin-bennett-msjc.blogspot.com/

Description: SCOM Rule that polls and logs APC UPS Units using Ralph Burri's custom snmp provider library. The OID's for the APC UPS units where looked up from SolarWinds.

References:
http://rburri.wordpress.com/2008/04/29/snmp-discovery-provider-for-opsmgr-2007/
http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx

POWERNET-MIB :: upsAdvOutputCurrent

Name
upsAdvOutputCurrent

Oid
1.3.6.1.4.1.318.1.1.1.4.2.4.0

Path
iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsOutput . upsAdvOutput . upsAdvOutputCurrent

Type
Gauge

Value-Ranges
0 to 4294967295

Access
read-only

Status
mandatory

Description

--------------------------------------------------------------------------------
The current in amperes drawn by the load on the UPS.

Element properties:

TargetCustom.JB.APC.Management.Pack.SNMPDevice
CategoryCustom
EnabledTrue
Alert GenerateFalse
RemotableTrue

Member Modules:

ID Module Type TypeId RunAs 
DS DataSource System.Performance.SnmpPerformanceProvider Default
WriteToDB WriteAction Microsoft.SystemCenter.CollectPerformanceData Default
WriteToDW WriteAction Microsoft.SystemCenter.DataWarehouse.PublishPerformanceData Default

Source Code:

<Rule ID="MomUIGeneratedRule5afcd98df6554058b3190d8862338e2c" Enabled="true" Target="Custom.JB.APC.Management.Pack.SNMPDevice" ConfirmDelivery="false" Remotable="true" Priority="Normal" DiscardLevel="100">
<Category>Custom</Category>
<DataSources>
<DataSource ID="DS" TypeID="Performance!System.Performance.SnmpPerformanceProvider">
<Interval>120</Interval>
<IsWriteAction>false</IsWriteAction>
<IP>$Target/Property[Type="NetLib!Microsoft.SystemCenter.NetworkDevice"]/IPAddress$</IP>
<CommunityString>$Target/Property[Type="NetLib!Microsoft.SystemCenter.NetworkDevice"]/CommunityString$</CommunityString>
<Version>$Target/Property[Type="NetLib!Microsoft.SystemCenter.NetworkDevice"]/Version$</Version>
<SnmpVarBinds>
<SnmpVarBind>
<OID>1.3.6.1.4.1.318.1.1.1.4.2.4.0</OID>
<Syntax>0</Syntax>
<Value VariantType="8"/>
</SnmpVarBind>
</SnmpVarBinds>
<ObjectName>Snmp Performance Object</ObjectName>
<CounterName>$data/SnmpVarBinds/SnmpVarBind[1]/OID$</CounterName>
<InstanceName>0</InstanceName>
<Value>$data/SnmpVarBinds/SnmpVarBind[1]/Value$</Value>
</DataSource>
</DataSources>
<WriteActions>
<WriteAction ID="WriteToDB" TypeID="SC!Microsoft.SystemCenter.CollectPerformanceData"/>
<WriteAction ID="WriteToDW" TypeID="SCDW!Microsoft.SystemCenter.DataWarehouse.PublishPerformanceData"/>
</WriteActions>
</Rule>