| DisplayName | Description | ID | Target | Category | Enabled | Instance Name | Counter Name | Frequency | Event_ID | Event Source | Alert Generate | Alert Severity | Alert Priority | Remotable | Event Log |
| SCUtils Management Pack for APC PDU License Check Rule | | SCUtils.APC.PDU.LicenseCheck.Rule | SCUtils.APC.PDU.Devices.Group | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Someone has attempted to login via the console with the incorrect password | | SCUtils.APC.PDU.Rule.accessViolationConsole | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - Someone has attempted to login via HTTP with the incorrect password | | SCUtils.APC.PDU.Rule.accessViolationHTTP | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - Trap used to test SNMP trap functionality | | SCUtils.APC.PDU.Rule.apcTestTrap | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - The specified PDU outlet has changed configuration. | | SCUtils.APC.PDU.Rule.configChangeOutlet | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The SNMP configuration has been changed | | SCUtils.APC.PDU.Rule.configChangeSNMP | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| APC PDU Disposal Rule | | SCUtils.APC.PDU.Rule.Disposal | SCUtils.APC.PDU.Devices.Group | Maintenance | True | | | 0 | 0 | | False | | | True | |
| PDU Trap Alert Rule - Probe 1 humidity threshold violated | | SCUtils.APC.PDU.Rule.humidityThresholdViolation1 | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Probe 2 humidity threshold violated | | SCUtils.APC.PDU.Rule.humidityThresholdViolation2 | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - An Environmental Monitor humidity threshold violation has been cleared on probe 1 | | SCUtils.APC.PDU.Rule.humidityThresholdViolationCleared1 | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - An Environmental Monitor humidity threshold violation has been cleared on probe 2 | | SCUtils.APC.PDU.Rule.humidityThresholdViolationCleared2 | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - The specified PDU outlet has turned off | | SCUtils.APC.PDU.Rule.outletOff | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The specified PDU outlet has turned on | | SCUtils.APC.PDU.Rule.outletOn | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The specified PDU outlet has rebooted | | SCUtils.APC.PDU.Rule.outletReboot | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The password for the device has been changed | | SCUtils.APC.PDU.Rule.passwordChange | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - PDU is in Atypical Bypass Mode | | SCUtils.APC.PDU.Rule.pduAtypicalBypassMode | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - Circuit Panel Input Frequency Out Of Range | | SCUtils.APC.PDU.Rule.pduCircuitPanelFrequencyOutOfRange | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Circuit Panel Input Frequency No Longer Out Of Range | | SCUtils.APC.PDU.Rule.pduCircuitPanelFrequencyOutofRangeCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Circuit Panel Input Overcurrent | | SCUtils.APC.PDU.Rule.pduCircuitPanelInputOvercurrent | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Circuit Panel Input Overcurrent Cleared | | SCUtils.APC.PDU.Rule.pduCircuitPanelInputOvercurrentCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Circuit Panel Input Overvoltage | | SCUtils.APC.PDU.Rule.pduCircuitPanelInputOvervoltage | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Circuit Panel Input Overvoltage Cleared | | SCUtils.APC.PDU.Rule.pduCircuitPanelInputOvervoltageCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Circuit Panel Input Undercurrent | | SCUtils.APC.PDU.Rule.pduCircuitPanelInputUndercurrent | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Circuit Panel Input Undercurrent Cleared | | SCUtils.APC.PDU.Rule.pduCircuitPanelInputUndercurrentCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Circuit Panel Input Undervoltage | | SCUtils.APC.PDU.Rule.pduCircuitPanelInputUndervoltage | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Circuit Panel Input Undervoltage Cleared | | SCUtils.APC.PDU.Rule.pduCircuitPanelInputUndervoltageCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Circuit Panel Input Neutral Overcurrent | | SCUtils.APC.PDU.Rule.pduCircuitPanelNeutralOvercurrent | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Circuit Panel Input Neutral Overcurrent Cleared | | SCUtils.APC.PDU.Rule.pduCircuitPanelNeutralOvercurrentCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Communication Established | | SCUtils.APC.PDU.Rule.pduCommunicationEstablished | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Communication Lost | | SCUtils.APC.PDU.Rule.pduCommunicationLost | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - A contact closure in the PDU is in an abnormal position | | SCUtils.APC.PDU.Rule.pduContactFault | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - A contact closure in the PDU is in a normal position | | SCUtils.APC.PDU.Rule.pduContactFaultCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - PDU is in Forced Bypass Mode | | SCUtils.APC.PDU.Rule.pduForcedBypassMode | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - Ground Overcurrent | | SCUtils.APC.PDU.Rule.pduGroundOvercurrent | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Ground Overcurrent Cleared | | SCUtils.APC.PDU.Rule.pduGroundOvercurrentCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Input Transformer Over Temperature | | SCUtils.APC.PDU.Rule.pduInputTransformerOverTemperature | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Input Transformer Over Temperature Cleared | | SCUtils.APC.PDU.Rule.pduInputTransformerOverTemperatureCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - PDU is in Maintenance Bypass Mode | | SCUtils.APC.PDU.Rule.pduMaintenanceBypassMode | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - PDU is in No Panel Feed Mode | | SCUtils.APC.PDU.Rule.pduNoPanelFeedMode | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - PDU is in On Battery Mode | | SCUtils.APC.PDU.Rule.pduOnBatteryMode | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - PDU System Off | | SCUtils.APC.PDU.Rule.pduSystemOff | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - UPS Input Voltage phase-N Lost | | SCUtils.APC.PDU.Rule.pduUPSInputVoltageLost | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - UPS Input Voltage phase-N Restored | | SCUtils.APC.PDU.Rule.pduUPSInputVoltageRestored | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - PDU is in Ups Operation Mode | | SCUtils.APC.PDU.Rule.pduUpsOperationMode | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Utility Line Overvoltage | | SCUtils.APC.PDU.Rule.pduUtilityLineOvervoltage | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Utility Line Overvoltage Cleared | | SCUtils.APC.PDU.Rule.pduUtilityLineOvervoltageCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Utility Line Undervoltage | | SCUtils.APC.PDU.Rule.pduUtilityLineUndervoltage | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Utility Line Undervoltage Cleared | | SCUtils.APC.PDU.Rule.pduUtilityLineUndervoltageCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A bank or phase on the Rack PDU has violated the low load threshold | | SCUtils.APC.PDU.Rule.rPDUBankPhaseLowLoad | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The bank or phase low load condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDUBankPhaseLowLoadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A bank or phase of the Rack PDU is near an overload condition | | SCUtils.APC.PDU.Rule.rPDUBankPhaseNearOverload | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The bank or phase near overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDUBankPhaseNearOverloadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A bank or phase of the Rack PDU is in an overload condition | | SCUtils.APC.PDU.Rule.rPDUBankPhaseOverload | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - The bank or phase overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDUBankPhaseOverloadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A cancel pending command has been made on a Switched Rack PDU | | SCUtils.APC.PDU.Rule.rPDUCancelPendingCommand | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Communication with a Rack PDU has been established | | SCUtils.APC.PDU.Rule.rPDUCommunicationEstablished | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Communication with a Rack PDU has been lost | | SCUtils.APC.PDU.Rule.rPDUCommunicationLost | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - A RPDU critical condition has been detected | | SCUtils.APC.PDU.Rule.rpduCriticalCondition | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | High | True | |
| PDU Trap Alert Rule - A RPDU critical condition has been cleared | | SCUtils.APC.PDU.Rule.rpduCriticalConditionCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A device configuration change has been made on a Rack PDU | | SCUtils.APC.PDU.Rule.rPDUDeviceConfigChange | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A RPDU informational condition has been detected. | | SCUtils.APC.PDU.Rule.rpduInformationalCondition | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A RPDU informational condition has been cleared. | | SCUtils.APC.PDU.Rule.rpduInformationalConditionCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| Phase/Bank Load Rule |
Getting this OID will return the phase/bank load measured in Amps.
| SCUtils.APC.PDU.Rule.rPDULoadStatusLoad | SCUtils.APC.PDU.PhaseBank | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| PDU Trap Alert Rule - A Rack PDU has violated the low load threshold | | SCUtils.APC.PDU.Rule.rPDULowLoad | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The low load condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDULowLoadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A Rack PDU is near an overload condition | | SCUtils.APC.PDU.Rule.rPDUNearOverload | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The near overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDUNearOverloadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - An outlet configuration change has been made on a Switched Rack PDU | | SCUtils.APC.PDU.Rule.rPDUOutletConfigChange | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A Rack PDU has violated the outlet low load threshold | | SCUtils.APC.PDU.Rule.rPDUOutletLowLoad | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The outlet low load condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDUOutletLowLoadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A Rack PDU is near an outlet overload condition | | SCUtils.APC.PDU.Rule.rPDUOutletNearOverload | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - The outlet near overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDUOutletNearOverloadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - An outlet on a Switched Rack PDU has turned off | | SCUtils.APC.PDU.Rule.rPDUOutletOff | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - An outlet on a Switched Rack PDU has turned on | | SCUtils.APC.PDU.Rule.rPDUOutletOn | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A Rack PDU is in an overload condition | | SCUtils.APC.PDU.Rule.rPDUOutletOverload | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - The outlet overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDUOutletOverloadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A Rack PDU is in an overload condition | | SCUtils.APC.PDU.Rule.rPDUOverload | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - The overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU.Rule.rPDUOverloadCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A phase configuration change has been made on a Rack PDU | | SCUtils.APC.PDU.Rule.rPDUPhaseConfigChange | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Power Supply 1 on Rack PDU is in FAIL state | | SCUtils.APC.PDU.Rule.rPDUPowerSupply1Fail | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Power Supply 1 on Rack PDU is operating normally | | SCUtils.APC.PDU.Rule.rPDUPowerSupply1Ok | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - Power Supply 2 on Rack PDU is in FAIL state | | SCUtils.APC.PDU.Rule.rPDUPowerSupply2Fail | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - Power Supply 2 on Rack PDU is operating normally | | SCUtils.APC.PDU.Rule.rPDUPowerSupply2Ok | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - A RPDU warning condition has been detected | | SCUtils.APC.PDU.Rule.rpduWarningCondition | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU Trap Alert Rule - A RPDU warning condition has been cleared | | SCUtils.APC.PDU.Rule.rpduWarningConditionCleared | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - An Environmental Monitor temperature threshold has been violated on probe 1 | | SCUtils.APC.PDU.Rule.temperatureThresholdViolation1 | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - An Environmental Monitor temperature threshold has been violated on probe 2 | | SCUtils.APC.PDU.Rule.temperatureThresholdViolation2 | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU Trap Alert Rule - An Environmental Monitor temperature threshold violation has been cleared on probe 1 | | SCUtils.APC.PDU.Rule.temperatureThresholdViolationCleared1 | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU Trap Alert Rule - An Environmental Monitor temperature threshold violation has been cleared on probe 2 | | SCUtils.APC.PDU.Rule.temperatureThresholdViolationCleared2 | SCUtils.APC.PDU | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| Bank current draw, in Amps Rule | Indicates the current draw, in Amps, of the load on the Rack PDU bank being queried | SCUtils.APC.PDU2.Bank.Rule.rPDU2BankStatusCurrent | SCUtils.APC.PDU2.Bank | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| PDU load in kiloVoltAmps (kVA) Rule | The apparent power consumption of the Rack PDU load in kiloVoltAmps (kVA) | SCUtils.APC.PDU2.Device.Rule.rPDU2DeviceStatusApparentPower | SCUtils.APC.PDU2.Device | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| PDU load energy Rule | A user resettable energy meter measuring Rack PDU load energy consumption in kilowatt-hours | SCUtils.APC.PDU2.Device.Rule.rPDU2DeviceStatusEnergy | SCUtils.APC.PDU2.Device | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| PDU load in kilowatts Rule | The power consumption of the Rack PDU load in kilowatts | SCUtils.APC.PDU2.Device.Rule.rPDU2DeviceStatusPower | SCUtils.APC.PDU2.Device | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Outlet current draw, in Amps Rule | Indicates the current draw, in Amps, of the load on the Rack PDU outlet being queried | SCUtils.APC.PDU2.OutletMetered.Rule.rPDU2OutletMeteredStatusCurrent | SCUtils.APC.PDU2.OutletMetered | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Outlet load energy consumption, in kilowatt-hours Rule | A user resettable energy meter measuring Rack PDU load energy consumption in kilowatt-hours | SCUtils.APC.PDU2.OutletMetered.Rule.rPDU2OutletMeteredStatusEnergy | SCUtils.APC.PDU2.OutletMetered | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Power draw of the load Rule | Indicates the power draw of the load on the Rack PDU outlet being queried | SCUtils.APC.PDU2.OutletMetered.Rule.rPDU2OutletMeteredStatusPower | SCUtils.APC.PDU2.OutletMetered | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Phase load apparent power in kiloVoltAmps (kVA) Rule | Indicates the load apparent power, in kiloVoltAmps (kVA), consumed on the Rack PDU phase being queried | SCUtils.APC.PDU2.Phase.Rule.rPDU2PhaseStatusApparentPower | SCUtils.APC.PDU2.Phase | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Phase current draw in Amps Rule | Indicates the current draw, in Amps, of the load on the Rack PDU phase being queried | SCUtils.APC.PDU2.Phase.Rule.rPDU2PhaseStatusCurrent | SCUtils.APC.PDU2.Phase | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Phase load power in kilowatts (kW) Rule | Indicates the load power, in kilowatts (kW), consumed on the Rack PDU phase being queried
| SCUtils.APC.PDU2.Phase.Rule.rPDU2PhaseStatusPower | SCUtils.APC.PDU2.Phase | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Phase load power factor Rule | Indicates the load power factor of the Rack PDU phase being queried
| SCUtils.APC.PDU2.Phase.Rule.rPDU2PhaseStatusPowerFactor | SCUtils.APC.PDU2.Phase | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Phase Voltage, in Volts Rule | Indicates the Voltage, in Volts, of the Rack PDU phase being queried | SCUtils.APC.PDU2.Phase.Rule.rPDU2PhaseStatusVoltage | SCUtils.APC.PDU2.Phase | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| PDU2 Trap Alert Rule - Someone has attempted to login via the console with the incorrect password | | SCUtils.APC.PDU2.Rule.accessViolationConsole | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - Someone has attempted to login via HTTP with the incorrect password | | SCUtils.APC.PDU2.Rule.accessViolationHTTP | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - Trap used to test SNMP trap functionality | | SCUtils.APC.PDU2.Rule.apcTestTrap | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - The specified PDU outlet has changed configuration. | | SCUtils.APC.PDU2.Rule.configChangeOutlet | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The SNMP configuration has been changed | | SCUtils.APC.PDU2.Rule.configChangeSNMP | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - Probe 1 humidity threshold violated | | SCUtils.APC.PDU2.Rule.humidityThresholdViolation1 | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Probe 2 humidity threshold violated | | SCUtils.APC.PDU2.Rule.humidityThresholdViolation2 | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - An Environmental Monitor humidity threshold violation has been cleared on probe 1 | | SCUtils.APC.PDU2.Rule.humidityThresholdViolationCleared1 | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - An Environmental Monitor humidity threshold violation has been cleared on probe 2 | | SCUtils.APC.PDU2.Rule.humidityThresholdViolationCleared2 | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - The specified PDU outlet has turned off | | SCUtils.APC.PDU2.Rule.outletOff | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The specified PDU outlet has turned on | | SCUtils.APC.PDU2.Rule.outletOn | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The specified PDU outlet has rebooted | | SCUtils.APC.PDU2.Rule.outletReboot | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The password for the device has been changed | | SCUtils.APC.PDU2.Rule.passwordChange | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - PDU is in Atypical Bypass Mode | | SCUtils.APC.PDU2.Rule.pduAtypicalBypassMode | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Frequency Out Of Range | | SCUtils.APC.PDU2.Rule.pduCircuitPanelFrequencyOutOfRange | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Frequency No Longer Out Of Range | | SCUtils.APC.PDU2.Rule.pduCircuitPanelFrequencyOutofRangeCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Overcurrent | | SCUtils.APC.PDU2.Rule.pduCircuitPanelInputOvercurrent | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Overcurrent Cleared | | SCUtils.APC.PDU2.Rule.pduCircuitPanelInputOvercurrentCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Overvoltage | | SCUtils.APC.PDU2.Rule.pduCircuitPanelInputOvervoltage | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Overvoltage Cleared | | SCUtils.APC.PDU2.Rule.pduCircuitPanelInputOvervoltageCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Undercurrent | | SCUtils.APC.PDU2.Rule.pduCircuitPanelInputUndercurrent | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Undercurrent Cleared | | SCUtils.APC.PDU2.Rule.pduCircuitPanelInputUndercurrentCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Undervoltage | | SCUtils.APC.PDU2.Rule.pduCircuitPanelInputUndervoltage | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Undervoltage Cleared | | SCUtils.APC.PDU2.Rule.pduCircuitPanelInputUndervoltageCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Neutral Overcurrent | | SCUtils.APC.PDU2.Rule.pduCircuitPanelNeutralOvercurrent | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Circuit Panel Input Neutral Overcurrent Cleared | | SCUtils.APC.PDU2.Rule.pduCircuitPanelNeutralOvercurrentCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Communication Established | | SCUtils.APC.PDU2.Rule.pduCommunicationEstablished | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Communication Lost | | SCUtils.APC.PDU2.Rule.pduCommunicationLost | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - A contact closure in the PDU is in an abnormal position | | SCUtils.APC.PDU2.Rule.pduContactFault | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - A contact closure in the PDU is in a normal position | | SCUtils.APC.PDU2.Rule.pduContactFaultCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - PDU is in Forced Bypass Mode | | SCUtils.APC.PDU2.Rule.pduForcedBypassMode | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - Ground Overcurrent | | SCUtils.APC.PDU2.Rule.pduGroundOvercurrent | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Ground Overcurrent Cleared | | SCUtils.APC.PDU2.Rule.pduGroundOvercurrentCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Input Transformer Over Temperature | | SCUtils.APC.PDU2.Rule.pduInputTransformerOverTemperature | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Input Transformer Over Temperature Cleared | | SCUtils.APC.PDU2.Rule.pduInputTransformerOverTemperatureCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - PDU is in Maintenance Bypass Mode | | SCUtils.APC.PDU2.Rule.pduMaintenanceBypassMode | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - PDU is in No Panel Feed Mode | | SCUtils.APC.PDU2.Rule.pduNoPanelFeedMode | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - PDU is in On Battery Mode | | SCUtils.APC.PDU2.Rule.pduOnBatteryMode | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - PDU System Off | | SCUtils.APC.PDU2.Rule.pduSystemOff | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - UPS Input Voltage phase-N Lost | | SCUtils.APC.PDU2.Rule.pduUPSInputVoltageLost | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - UPS Input Voltage phase-N Restored | | SCUtils.APC.PDU2.Rule.pduUPSInputVoltageRestored | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - PDU is in Ups Operation Mode | | SCUtils.APC.PDU2.Rule.pduUpsOperationMode | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Utility Line Overvoltage | | SCUtils.APC.PDU2.Rule.pduUtilityLineOvervoltage | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Utility Line Overvoltage Cleared | | SCUtils.APC.PDU2.Rule.pduUtilityLineOvervoltageCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Utility Line Undervoltage | | SCUtils.APC.PDU2.Rule.pduUtilityLineUndervoltage | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Utility Line Undervoltage Cleared | | SCUtils.APC.PDU2.Rule.pduUtilityLineUndervoltageCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A bank or phase on the Rack PDU has violated the low load threshold | | SCUtils.APC.PDU2.Rule.rPDUBankPhaseLowLoad | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The bank or phase low load condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDUBankPhaseLowLoadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A bank or phase of the Rack PDU is near an overload condition | | SCUtils.APC.PDU2.Rule.rPDUBankPhaseNearOverload | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The bank or phase near overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDUBankPhaseNearOverloadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A bank or phase of the Rack PDU is in an overload condition | | SCUtils.APC.PDU2.Rule.rPDUBankPhaseOverload | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - The bank or phase overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDUBankPhaseOverloadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A cancel pending command has been made on a Switched Rack PDU | | SCUtils.APC.PDU2.Rule.rPDUCancelPendingCommand | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Communication with a Rack PDU has been established | | SCUtils.APC.PDU2.Rule.rPDUCommunicationEstablished | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Communication with a Rack PDU has been lost | | SCUtils.APC.PDU2.Rule.rPDUCommunicationLost | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - A RPDU critical condition has been detected | | SCUtils.APC.PDU2.Rule.rpduCriticalCondition | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | High | True | |
| PDU2 Trap Alert Rule - A RPDU critical condition has been cleared | | SCUtils.APC.PDU2.Rule.rpduCriticalConditionCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A device configuration change has been made on a Rack PDU | | SCUtils.APC.PDU2.Rule.rPDUDeviceConfigChange | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A RPDU informational condition has been detected. | | SCUtils.APC.PDU2.Rule.rpduInformationalCondition | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A RPDU informational condition has been cleared. | | SCUtils.APC.PDU2.Rule.rpduInformationalConditionCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A Rack PDU has violated the low load threshold | | SCUtils.APC.PDU2.Rule.rPDULowLoad | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The low load condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDULowLoadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A Rack PDU is near an overload condition | | SCUtils.APC.PDU2.Rule.rPDUNearOverload | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The near overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDUNearOverloadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - An outlet configuration change has been made on a Switched Rack PDU | | SCUtils.APC.PDU2.Rule.rPDUOutletConfigChange | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A Rack PDU has violated the outlet low load threshold | | SCUtils.APC.PDU2.Rule.rPDUOutletLowLoad | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The outlet low load condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDUOutletLowLoadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A Rack PDU is near an outlet overload condition | | SCUtils.APC.PDU2.Rule.rPDUOutletNearOverload | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - The outlet near overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDUOutletNearOverloadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - An outlet on a Switched Rack PDU has turned off | | SCUtils.APC.PDU2.Rule.rPDUOutletOff | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - An outlet on a Switched Rack PDU has turned on | | SCUtils.APC.PDU2.Rule.rPDUOutletOn | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A Rack PDU is in an overload condition | | SCUtils.APC.PDU2.Rule.rPDUOutletOverload | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - The outlet overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDUOutletOverloadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A Rack PDU is in an overload condition | | SCUtils.APC.PDU2.Rule.rPDUOverload | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - The overload condition on a Rack PDU has been cleared | | SCUtils.APC.PDU2.Rule.rPDUOverloadCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A phase configuration change has been made on a Rack PDU | | SCUtils.APC.PDU2.Rule.rPDUPhaseConfigChange | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Power Supply 1 on Rack PDU is in FAIL state | | SCUtils.APC.PDU2.Rule.rPDUPowerSupply1Fail | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Power Supply 1 on Rack PDU is operating normally | | SCUtils.APC.PDU2.Rule.rPDUPowerSupply1Ok | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - Power Supply 2 on Rack PDU is in FAIL state | | SCUtils.APC.PDU2.Rule.rPDUPowerSupply2Fail | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - Power Supply 2 on Rack PDU is operating normally | | SCUtils.APC.PDU2.Rule.rPDUPowerSupply2Ok | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - A RPDU warning condition has been detected | | SCUtils.APC.PDU2.Rule.rpduWarningCondition | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Warning | Normal | True | |
| PDU2 Trap Alert Rule - A RPDU warning condition has been cleared | | SCUtils.APC.PDU2.Rule.rpduWarningConditionCleared | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - An Environmental Monitor temperature threshold has been violated on probe 1 | | SCUtils.APC.PDU2.Rule.temperatureThresholdViolation1 | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - An Environmental Monitor temperature threshold has been violated on probe 2 | | SCUtils.APC.PDU2.Rule.temperatureThresholdViolation2 | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Error | Normal | True | |
| PDU2 Trap Alert Rule - An Environmental Monitor temperature threshold violation has been cleared on probe 1 | | SCUtils.APC.PDU2.Rule.temperatureThresholdViolationCleared1 | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| PDU2 Trap Alert Rule - An Environmental Monitor temperature threshold violation has been cleared on probe 2 | | SCUtils.APC.PDU2.Rule.temperatureThresholdViolationCleared2 | SCUtils.APC.PDU2 | Alert | True | | | 0 | 0 | | True | Information | Low | True | |
| Sensor humidity reading in percent relative humidity Rule | Sensor humidity reading in percent relative humidity | SCUtils.APC.PDU2.Sensor.Rule.rPDU2SensorTempHumidityStatusRelativeHumidity | SCUtils.APC.PDU2.Sensor | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Sensor temperature reading in degrees Celsius Rule | Sensor temperature reading in degrees Celsius | SCUtils.APC.PDU2.Sensor.Rule.rPDU2SensorTempHumidityStatusTempC | SCUtils.APC.PDU2.Sensor | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |
| Sensor temperature reading in degrees Fahrenheit Rule | Sensor temperature reading in degrees Fahrenheit | SCUtils.APC.PDU2.Sensor.Rule.rPDU2SensorTempHumidityStatusTempF | SCUtils.APC.PDU2.Sensor | PerformanceCollection | True | | | 0 | 0 | | False | | | True | |