All Rules in Sample.APC Management Pack

 DisplayNameDescriptionIDTargetCategoryEnabledInstance NameCounter NameFrequencyEvent_IDEvent SourceAlert GenerateAlert SeverityAlert PriorityRemotableEvent Log
Sample.APC.PDU.Rule.rPDULoadStatusLoadStateSample APC PDU Load StatusSCOM Rule that polls and logs APC PDU Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : rPDULoadStatusLoadState Name rPDULoadStatusLoadState Oid 1.3.6.1.4.1.318.1.1.12.2.3.1.1.3.1 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . rPDU . rPDULoad . rPDULoadStatus . rPDULoadStatusTable . rPDULoadStatusEntry . rPDULoadStatusLoadState Type Integer Known Values phaseLoadNormal (1) phaseLoadLow (2) phaseLoadNearOverload (3) phaseLoadOverload (4) Access read-only Status mandatory Description Getting this OID will return the phase/bank load state. phaseLoadNormal(1) indicates that the phase/bank is operating properly within the rPDULoadConfigLowLoadThreshold and rPDULoadConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the phase/bank load has dropped below the rPDULoadConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadNearOverload(3) indicates that the phase/bank load is greater than or equal to the rPDULoadConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadOverload(4) indicates that the phase/bank load is greater than or equal to the rPDULoadConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. Sample.APC.PDU.Rule.rPDULoadStatusLoadStateSample.APC.PDU.DevicePerformanceCollectionFalse00FalseTrue
Sample.APC.PDU.Rule.rPDUPowerSupply1StatusSample APC PDU Power Supply 1 StatusSCOM Rule that polls and logs APC PDU Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : rPDUPowerSupply1Status Name rPDUPowerSupply1Status Oid 1.3.6.1.4.1.318.1.1.12.4.1.1.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . rPDU . rPDUPowerSupply . rPDUPowerSupplyDevice . rPDUPowerSupply1Status Type Integer Known Values PowerSupply1Ok (1) PowerSupply1Failed (2) Access read-only Status mandatory Description Getting this OID will return powerSupply1Ok(1) if power supply 1 is functioning normally. If not functioning normally, this OID will return powerSupply1Failed(2). Sample.APC.PDU.Rule.rPDUPowerSupply1StatusSample.APC.PDU.DevicePerformanceCollectionFalse00FalseTrue
Sample.APC.PDU.Rule.rPDUPowerSupply2StatusSample APC PDU Power Supply 2 StatusSCOM Rule that polls and logs APC PDU Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : rPDUPowerSupply2Status Name rPDUPowerSupply2Status 1.3.6.1.4.1.318.1.1.12.4.1.2.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . rPDU . rPDUPowerSupply . rPDUPowerSupplyDevice . rPDUPowerSupply2Status Type Integer Known Values PowerSupply2Ok (1) PowerSupply2Failed (2) Access read-only Status mandatory Description Getting this OID will return powerSupply2Ok(1) if power supply 2 is functioning normally. If not functioning normally, this OID will return powerSupply2Failed(2). Sample.APC.PDU.Rule.rPDUPowerSupply2StatusSample.APC.PDU.DevicePerformanceCollectionFalse00FalseTrue
Sample.APC.UPS.Rule.upsAdvBatteryCapacitySample APC Ups Battery CapacitySCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvBatteryCapacity Name upsAdvBatteryCapacity Oid 1.3.6.1.4.1.318.1.1.1.2.2.1.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsBattery . upsAdvBattery . upsAdvBatteryCapacity Type Gauge Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The remaining battery capacity expressed in percent of full capacity.Sample.APC.UPS.Rule.upsAdvBatteryCapacitySample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsAdvBatteryRunTimeRemainingSample APC Ups Battery RunTime RemainingSCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvBatteryRunTimeRemaining Name upsAdvBatteryRunTimeRemaining Oid 1.3.6.1.4.1.318.1.1.1.2.2.3.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsBattery . upsAdvBattery . upsAdvBatteryRunTimeRemaining Type TimeTicks Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The UPS battery run time remaining before battery exhaustion.Sample.APC.UPS.Rule.upsAdvBatteryRunTimeRemainingSample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsAdvBatteryTemperatureSample APC Ups Battery TemperatureSCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvBatteryTemperature Name upsAdvBatteryTemperature Oid 1.3.6.1.4.1.318.1.1.1.2.2.2.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsBattery . upsAdvBattery . upsAdvBatteryTemperature Type Gauge Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The current internal UPS temperature expressed in Celsius.Sample.APC.UPS.Rule.upsAdvBatteryTemperatureSample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsAdvInputFrequencySample APC Ups Input FrequencySCOM Rule that polls and logs APC UPS Units. http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvInputFrequency Name upsAdvInputFrequency Oid 1.3.6.1.4.1.318.1.1.1.3.2.4.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsInput . upsAdvInput . upsAdvInputFrequency Type Gauge Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The current input frequency to the UPS system in Hz.Sample.APC.UPS.Rule.upsAdvInputFrequencySample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsAdvInputLineVoltageSample APC Ups Input Line VoltageSCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvInputLineVoltage Name upsAdvInputLineVoltage Oid 1.3.6.1.4.1.318.1.1.1.3.2.1.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsInput . upsAdvInput . upsAdvInputLineVoltage Type Gauge Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The current utility line voltage in VAC.Sample.APC.UPS.Rule.upsAdvInputLineVoltageSample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsAdvOutputCurrentSample APC Ups Output CurrentSCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvOutputCurrent Name upsAdvOutputCurrent Oid 1.3.6.1.4.1.318.1.1.1.4.2.4.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsOutput . upsAdvOutput . upsAdvOutputCurrent Type Gauge Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The current in amperes drawn by the load on the UPS.Sample.APC.UPS.Rule.upsAdvOutputCurrentSample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsAdvOutputFrequencySample APC Ups Output FrequencySCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvOutputFrequency Name upsAdvOutputFrequency Oid 1.3.6.1.4.1.318.1.1.1.4.2.2.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsOutput . upsAdvOutput . upsAdvOutputFrequency Type Gauge Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The current output frequency of the UPS system in Hz.Sample.APC.UPS.Rule.upsAdvOutputFrequencySample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsAdvOutputLoadSample APC Ups Output LoadSCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvOutputLoad Name upsAdvOutputLoad Oid 1.3.6.1.4.1.318.1.1.1.4.2.3.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsOutput . upsAdvOutput . upsAdvOutputLoad Type Gauge Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The current UPS load expressed in percent of rated capacity.Sample.APC.UPS.Rule.upsAdvOutputLoadSample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsAdvOutputVoltageSample APC Ups Output VoltageSCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsAdvOutputVoltage Name upsAdvOutputVoltage Oid 1.3.6.1.4.1.318.1.1.1.4.2.1.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsOutput . upsAdvOutput . upsAdvOutputVoltage Type Gauge Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The output voltage of the UPS system in VAC.Sample.APC.UPS.Rule.upsAdvOutputVoltageSample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsBasicBatteryStatusSample APC Ups Basic Battery StatusSCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsBasicBatteryStatus Name upsBasicBatteryStatus Oid 1.3.6.1.4.1.318.1.1.1.2.1.1.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsBattery . upsBasicBattery . upsBasicBatteryStatus Base-Type integer Known-Values unknown (1) batteryNormal (2) batteryLow (3) Access read-only Status mandatory Description -------------------------------------------------------------------------------- The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime.Sample.APC.UPS.Rule.upsBasicBatteryStatusSample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue
Sample.APC.UPS.Rule.upsBasicBatteryTimeOnBatterySample APC Ups Time On BatterySCOM Rule that polls and logs APC UPS Units. References: http://support.ipmonitor.com/mibs/POWERNET-MIB/info.aspx POWERNET-MIB : upsBasicBatteryTimeOnBattery Name upsBasicBatteryTimeOnBattery Oid 1.3.6.1.4.1.318.1.1.1.2.1.2.0 Path iso . org . dod . internet . private . enterprises . apc . products . hardware . ups . upsBattery . upsBasicBattery . upsBasicBatteryTimeOnBattery Type TimeTicks Value-Ranges 0 to 4294967295 Access read-only Status mandatory Description -------------------------------------------------------------------------------- The elapsed time since the UPS has switched to battery power.Sample.APC.UPS.Rule.upsBasicBatteryTimeOnBatterySample.APC.UPS.DevicePerformanceCollectionTrue00FalseTrue