iem Status Probe Current Humidy High

SCUtils.APC.UPS.Monitor.iem.StatusProbeCurrentHumidyHigh (UnitMonitor)


The current humidity reading from the probe in percent relative humidity. Healthy if than 40-55.

Element properties:

TargetSCUtils.APC.UPS.IEMProbe
Parent MonitorSystem.Health.AvailabilityState
CategoryAvailabilityHealth
EnabledTrue
Alert GenerateTrue
Alert SeverityWarning
Alert PriorityNormal
Alert Auto ResolveTrue
Monitor TypeSCUtils.APC.UPS.Monitor.Type.GreaterThanThresholdProbe
RemotableTrue
AccessibilityPublic
Alert Message
iem Status Probe Current Humidy High

Sourse: {0}
Location: {1}
Primary Owner: {2}
IP : {3}
Probe Name : {4}
Value : {5}

The current humidity reading from the probe in percent relative humidity. Healthy if than 40-55.
RunAsDefault

Source Code:

<UnitMonitor ID="SCUtils.APC.UPS.Monitor.iem.StatusProbeCurrentHumidyHigh" Accessibility="Public" Enabled="true" Target="SCUtils.APC.UPS.IEMProbe" ParentMonitorID="Health!System.Health.AvailabilityState" Remotable="true" Priority="Normal" TypeID="SCUtils.APC.UPS.Monitor.Type.GreaterThanThresholdProbe" ConfirmDelivery="true">
<Category>AvailabilityHealth</Category>
<AlertSettings AlertMessage="SCUtils.APC.UPS.Monitor.iem.StatusProbeCurrentHumidyHigh_AlertMessageResourceID">
<AlertOnState>Warning</AlertOnState>
<AutoResolve>true</AutoResolve>
<AlertPriority>Normal</AlertPriority>
<AlertSeverity>Warning</AlertSeverity>
<AlertParameters>
<AlertParameter1>$Target/Host/Host/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/sysName$</AlertParameter1>
<AlertParameter2>$Target/Host/Host/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/Location$</AlertParameter2>
<AlertParameter3>$Target/Host/Host/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/PrimaryOwnerContact$</AlertParameter3>
<AlertParameter4>$Target/Host/Host/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPAddress$</AlertParameter4>
<AlertParameter5>$Target/Property[Type="SCUtils.APC.UPS.IEMProbe"]/ProbeName$</AlertParameter5>
<AlertParameter6>$Data/Context/SnmpVarBinds/SnmpVarBind[1]/Value$</AlertParameter6>
</AlertParameters>
</AlertSettings>
<OperationalStates>
<OperationalState ID="SCUtils.APC.UPS.Monitor.iem.StatusProbeCurrentHumidyHigh.Success" MonitorTypeStateID="StatusOK" HealthState="Success"/>
<OperationalState ID="SCUtils.APC.UPS.Monitor.iem.StatusProbeCurrentHumidyHigh.Error" MonitorTypeStateID="StatusNotOK" HealthState="Warning"/>
</OperationalStates>
<Configuration>
<IntervalSeconds>600</IntervalSeconds>
<IPAddress>$Target/Host/Host/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPAddress$</IPAddress>
<CommunityString>$RunAs[Name="NetworkLibrary!System.NetworkManagement.Snmp.MonitoringAccount"]/CommunityString$</CommunityString>
<SnmpVersion>$Target/Host/Host/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPVersion$</SnmpVersion>
<OID>.1.3.6.1.4.1.318.1.1.10.2.3.2.1.6.$Target/Property[Type="SCUtils.APC.UPS.IEMProbe"]/Index$</OID>
<Threshold>55</Threshold>
</Configuration>
</UnitMonitor>