| DisplayName | ID | Target | Category | Enabled | Alert Generate |
| Environment Humidity | SCUtils.APC.UPS.Rule.Collect.UPSIEMProbeHumidity | SCUtils.APC.UPS.IEMProbe | PerformanceCollection | True | False |
| Environment temperature | SCUtils.APC.UPS.Rule.Collect.UPSIEMProbeTemp | SCUtils.APC.UPS.IEMProbe | PerformanceCollection | True | False |
| UPS Battery Capacity | SCUtils.APC.UPS.Rule.ups.AdvBatteryCapacity | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Battery RunTime Remaining | SCUtils.APC.UPS.Rule.ups.AdvBatteryRunTimeRemaining | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Battery Temperature | SCUtils.APC.UPS.Rule.ups.AdvBatteryTemperature | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Input Frequency | SCUtils.APC.UPS.Rule.ups.AdvInputFrequency | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Input Line Voltage | SCUtils.APC.UPS.Rule.ups.AdvInputLineVoltage | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Output Current | SCUtils.APC.UPS.Rule.ups.AdvOutputCurrent | SCUtils.APC.UPS | PerformanceCollection | False | False |
| UPS Output Frequency | SCUtils.APC.UPS.Rule.ups.AdvOutputFrequency | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Output Load | SCUtils.APC.UPS.Rule.ups.AdvOutputLoad | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Output Voltage | SCUtils.APC.UPS.Rule.ups.AdvOutputVoltage | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Time On Battery | SCUtils.APC.UPS.Rule.ups.BasicBattery.TimeOnBattery | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Basic Battery Status | SCUtils.APC.UPS.Rule.ups.BasicBatteryStatus | SCUtils.APC.UPS | PerformanceCollection | True | False |
| UPS Alert trap Rule - An internal UPS communication fault exists | SCUtils.APC.UPS.Trap.Rule.apcInternalCommunicationFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An internal UPS communication fault no longer exists | SCUtils.APC.UPS.Trap.Rule.apcInternalCommunicationFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Test SNMP trap | SCUtils.APC.UPS.Trap.Rule.apcTestTrap | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The output voltage is not within acceptable range | SCUtils.APC.UPS.Trap.Rule.badVoltage | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The output voltage has returned to an acceptable level | SCUtils.APC.UPS.Trap.Rule.badVoltageCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Base module fan needs repair | SCUtils.APC.UPS.Trap.Rule.baseFanFailure | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The battery temperature threshold has been violated | SCUtils.APC.UPS.Trap.Rule.batteryOverTemperature | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The battery over temperature has been cleared | SCUtils.APC.UPS.Trap.Rule.batteryOverTemperatureCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS is communicating with the external battery packs | SCUtils.APC.UPS.Trap.Rule.batteryPackCommEstablished | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Check installation of external battery packs signal cable | SCUtils.APC.UPS.Trap.Rule.batteryPackCommLost | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Base module bypass power supply needs repair | SCUtils.APC.UPS.Trap.Rule.bypassPowerSupplyFailure | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has finished calibrating | SCUtils.APC.UPS.Trap.Rule.calibrationEnd | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A battery calibration test has been initiated on the UPS | SCUtils.APC.UPS.Trap.Rule.calibrationStart | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The battery charger has failed | SCUtils.APC.UPS.Trap.Rule.chargerFailure | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The battery charger failure condition has been cleared | SCUtils.APC.UPS.Trap.Rule.chargerFailureCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Authentication on agent code image is done | SCUtils.APC.UPS.Trap.Rule.codeAuthenticationDone | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Communication with the UPS has been established | SCUtils.APC.UPS.Trap.Rule.communicationEstablished | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Communication to the UPS has been lost | SCUtils.APC.UPS.Trap.Rule.communicationLost | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - One of the contacts on the Environmental Monitor has changed from its default position | SCUtils.APC.UPS.Trap.Rule.contactFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A fault on one of the Environmental Monitor contacts has been resolved | SCUtils.APC.UPS.Trap.Rule.contactFaultResolved | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A UPS discharge condition has been cleared | SCUtils.APC.UPS.Trap.Rule.dischargeCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A graceful shutdown has been initiated | SCUtils.APC.UPS.Trap.Rule.gracefulShutdown | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS on bypass due to internal fault | SCUtils.APC.UPS.Trap.Rule.hardwareFailureBypass | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Probe 1 humidity threshold violated | SCUtils.APC.UPS.Trap.Rule.humidityThresholdViolation1 | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An Environmental Monitor humidity threshold has been violated on probe 2 | SCUtils.APC.UPS.Trap.Rule.humidityThresholdViolation2 | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An Environmental Monitor humidity threshold violation has been cleared on probe 1 | SCUtils.APC.UPS.Trap.Rule.humidityThresholdViolationCleared1 | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An Environmental Monitor humidity threshold violation has been cleared on probe 2 | SCUtils.APC.UPS.Trap.Rule.humidityThresholdViolationCleared2 | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS batteries are low | SCUtils.APC.UPS.Trap.Rule.lowBattery | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Communication to the UPS when the UPS is on Battery | SCUtils.APC.UPS.Trap.Rule.onbatterycommunicationLost | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Utility power has been restored | SCUtils.APC.UPS.Trap.Rule.powerRestored | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Agent restarting as commanded by manager | SCUtils.APC.UPS.Trap.Rule.restartAgent | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS has returned from bypass | SCUtils.APC.UPS.Trap.Rule.returnFromBypass | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has returned from a low battery condition | SCUtils.APC.UPS.Trap.Rule.returnFromLowBattery | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS is reducing the line voltage via SmartTrim(TM) | SCUtils.APC.UPS.Trap.Rule.smartAvrReducing | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has returned from SmartTrim(TM) | SCUtils.APC.UPS.Trap.Rule.smartAvrReducingOff | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has returned from SmartBoost(TM) | SCUtils.APC.UPS.Trap.Rule.smartBoostOff | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has enabled SmartBoost(TM) | SCUtils.APC.UPS.Trap.Rule.smartBoostOn | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - SmartBoost(TM) or SmartTrim(TM) relay fault | SCUtils.APC.UPS.Trap.Rule.smartRelayFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared | SCUtils.APC.UPS.Trap.Rule.smartRelayFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS on bypass - user set | SCUtils.APC.UPS.Trap.Rule.softwareBypass | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS on bypass | SCUtils.APC.UPS.Trap.Rule.switchedBypass | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An Environmental Monitor temperature threshold has been violated on probe 1 | SCUtils.APC.UPS.Trap.Rule.temperatureThresholdViolation1 | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An Environmental Monitor temperature threshold has been violated on probe 2 | SCUtils.APC.UPS.Trap.Rule.temperatureThresholdViolation2 | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An Environmental Monitor temperature threshold violation has been cleared on probe 1 | SCUtils.APC.UPS.Trap.Rule.temperatureThresholdViolationCleared1 | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An Environmental Monitor temperature threshold violation has been cleared on probe 2 | SCUtils.APC.UPS.Trap.Rule.temperatureThresholdViolationCleared2 | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The backfeed relay has a fault | SCUtils.APC.UPS.Trap.Rule.upsBackfeedRelayFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The backfeed relay has a fault cleared | SCUtils.APC.UPS.Trap.Rule.upsBackfeedRelayFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The batteries of the UPS need immediate replacement | SCUtils.APC.UPS.Trap.Rule.upsBatteryNeedsReplacement | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A bad battery fault has been cleared | SCUtils.APC.UPS.Trap.Rule.upsBatteryReplaced | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A battery bus soft start fault exists | SCUtils.APC.UPS.Trap.Rule.upsBatterySoftBusStartFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A battery bus soft start fault exists cleared | SCUtils.APC.UPS.Trap.Rule.upsBatterySoftBusStartFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The battery temperature sensor fault exists | SCUtils.APC.UPS.Trap.Rule.upsBatteryTempSensorFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The battery temperature sensor fault cleared | SCUtils.APC.UPS.Trap.Rule.upsBatteryTempSensorFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A bypass relay has a fault | SCUtils.APC.UPS.Trap.Rule.upsBypassRelayFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A bypass relay has a fault cleared | SCUtils.APC.UPS.Trap.Rule.upsBypassRelayFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A calibration value in the stack was changed | SCUtils.APC.UPS.Trap.Rule.upsCalibrationStackChanged | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A UPS critical condition was detected | SCUtils.APC.UPS.Trap.Rule.upsCriticalCondition | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A UPS critical condition has been cleared | SCUtils.APC.UPS.Trap.Rule.upsCriticalConditionCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS failed its internal diagnostic self-test | SCUtils.APC.UPS.Trap.Rule.upsDiagnosticsFailed | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS passed its internal self-test | SCUtils.APC.UPS.Trap.Rule.upsDiagnosticsPassed | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The dip switch settings on the UPS have been changed | SCUtils.APC.UPS.Trap.Rule.upsDipSwitchChanged | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS batteries are discharged | SCUtils.APC.UPS.Trap.Rule.upsDischarged | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Emergency Power Off (EPO) active | SCUtils.APC.UPS.Trap.Rule.upsEPOActive | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Emergency Power Off (EPO) now inactive | SCUtils.APC.UPS.Trap.Rule.upsEPOActiveCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A firmware mismatch error exists | SCUtils.APC.UPS.Trap.Rule.upsFirmwareMismatch | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A firmware mismatch error no longer exists | SCUtils.APC.UPS.Trap.Rule.upsFirmwareMismatchCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS firmware update failed | SCUtils.APC.UPS.Trap.Rule.upsFirmwareUpdateFailed | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Finished updating UPS firmware | SCUtils.APC.UPS.Trap.Rule.upsFirmwareUpdateFinished | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - Updating UPS firmware | SCUtils.APC.UPS.Trap.Rule.upsFirmwareUpdateStarted | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS firmware update succeeded | SCUtils.APC.UPS.Trap.Rule.upsFirmwareUpdateSucceeded | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS has no valid firmware | SCUtils.APC.UPS.Trap.Rule.upsHasNoValidFirmware | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS now has a valid firmware | SCUtils.APC.UPS.Trap.Rule.upsHasNoValidFirmwareCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A UPS informational condition has been detected | SCUtils.APC.UPS.Trap.Rule.upsInformationalCondition | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A UPS informational condition has been cleared | SCUtils.APC.UPS.Trap.Rule.upsInformationalConditionCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The internal over temperature condition exists | SCUtils.APC.UPS.Trap.Rule.upsInternalOverTemperature | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The internal over temperature condition cleared | SCUtils.APC.UPS.Trap.Rule.upsInternalOverTemperatureCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The inverter fault exists | SCUtils.APC.UPS.Trap.Rule.upsInverterFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The inverter fault cleared | SCUtils.APC.UPS.Trap.Rule.upsInverterFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A local display button fault exists | SCUtils.APC.UPS.Trap.Rule.upsLocalDisplayButtonFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A local display button fault no longer exists | SCUtils.APC.UPS.Trap.Rule.upsLocalDisplayButtonFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The MPU has been reset | SCUtils.APC.UPS.Trap.Rule.upsMpuReset | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS needs factory setup | SCUtils.APC.UPS.Trap.Rule.upsNeedsFactorySetupFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - UPS no longer needs factory setup | SCUtils.APC.UPS.Trap.Rule.upsNeedsFactorySetupFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has switched to battery backup power | SCUtils.APC.UPS.Trap.Rule.upsOnBattery | SCUtils.APC.UPS | Alert | True | True |
|
UPS Alert trap Rule - The UPS is on battery due to an error.
| SCUtils.APC.UPS.Trap.Rule.upsOnBatteryDueToFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS is no longer on battery due to an error | SCUtils.APC.UPS.Trap.Rule.upsOnBatteryDueToFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An oscillator error exists | SCUtils.APC.UPS.Trap.Rule.upsOscillatorFailed | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - An oscillator error no longer exists | SCUtils.APC.UPS.Trap.Rule.upsOscillatorFailedCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The specified Outlet Group command has been issued | SCUtils.APC.UPS.Trap.Rule.upsOutletGroupCommand | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The specified Outlet Group turned off | SCUtils.APC.UPS.Trap.Rule.upsOutletGroupTurnedOff | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The specified Outlet Group turned on | SCUtils.APC.UPS.Trap.Rule.upsOutletGroupTurnedOn | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The Output Switch is closed | SCUtils.APC.UPS.Trap.Rule.upsOutputSwitchClosed | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The Output Switch is open | SCUtils.APC.UPS.Trap.Rule.upsOutputSwitchOpened | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS overload | SCUtils.APC.UPS.Trap.Rule.upsOverload | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The overload condition has been cleared | SCUtils.APC.UPS.Trap.Rule.upsOverloadCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A PFC fault exists | SCUtils.APC.UPS.Trap.Rule.upsPfcFault | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The PFC fault cleared | SCUtils.APC.UPS.Trap.Rule.upsPfcFaultCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has started its reboot sequence | SCUtils.APC.UPS.Trap.Rule.upsRebootStarted | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS is entering 'sleep' mode | SCUtils.APC.UPS.Trap.Rule.upsSleeping | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has been turned 'off' | SCUtils.APC.UPS.Trap.Rule.upsTurnedOff | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A UPS is turned on | SCUtils.APC.UPS.Trap.Rule.upsTurnedOn | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A UPS warning condition has been detected | SCUtils.APC.UPS.Trap.Rule.upsWarningCondition | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - A UPS warning condition has been cleared | SCUtils.APC.UPS.Trap.Rule.upsWarningConditionCleared | SCUtils.APC.UPS | Alert | True | True |
| UPS Alert trap Rule - The UPS has returned from 'sleep' mode | SCUtils.APC.UPS.Trap.Rule.upsWokeUp | SCUtils.APC.UPS | Alert | True | True |