| DisplayName | Description | ID | Target | Parent Monitor | Category | Enabled | Instance Name | Counter Name | Frequency | Alert Generate | Alert Severity | Alert Priority | Alert Auto Resolve | Monitor Type | Remotable | Accessibility | RunAs |
| iem Status Probe Current Humidy High |
The current humidity reading from the probe in percent relative humidity. Healthy if than 40-55.
| SCUtils.APC.UPS.Monitor.iem.StatusProbeCurrentHumidyHigh | SCUtils.APC.UPS.IEMProbe | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.GreaterThanThresholdProbe | True | Public | |
| iem Status Probe Current Humidy Low |
The current humidity reading from the probe in percent relative humidity. Healthy if than 40-55.
| SCUtils.APC.UPS.Monitor.iem.StatusProbeCurrentHumidyLow | SCUtils.APC.UPS.IEMProbe | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.LessThanThresholdProbe | True | Public | |
| iem Status Probe High Temperature |
Probe temperature reading.
| SCUtils.APC.UPS.Monitor.iem.StatusProbeHighTemp | SCUtils.APC.UPS.IEMProbe | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.IntEnvMonProbeTemperature | True | Public | |
| UPS Battery Capacity |
Healthy if greater than or equal to 60 percent. The remaining battery capacity expressed in percent of full capacity.
| SCUtils.APC.UPS.Monitor.ups.AdvBatteryCapacity | SCUtils.APC.UPS | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.LessThanThresholdProbe | True | Public | |
| UPS Number Of Bad Battery Packs | The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. | SCUtils.APC.UPS.Monitor.ups.AdvBatteryNumOfBadBattPacks | SCUtils.APC.UPS | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.StatusProbe | True | Public | |
| UPS Battery Replacement Indicator |
Healthy if not equal to 2. Monitor warning indicates that there is a UPS battery that needs to be changed. The UPS may not perform as desired should a power failure occur.
| SCUtils.APC.UPS.Monitor.ups.AdvBatteryReplaceIndicator | SCUtils.APC.UPS | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.StatusProbe | True | Public | |
| UPS Battery RunTime Remaining | | SCUtils.APC.UPS.Monitor.ups.AdvBatteryRunTimeRemaining | SCUtils.APC.UPS | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Error | Normal | True | SCUtils.APC.UPS.Monitor.Type.BatteryRunTime | True | Public | |
| UPS Battery Temperature | | SCUtils.APC.UPS.Monitor.ups.AdvBatteryTemperature | SCUtils.APC.UPS | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.GreaterThanThresholdProbe | True | Public | |
| UPS Output Load |
Healthy if less than 50.The current UPS load expressed in percent of rated capacity.
| SCUtils.APC.UPS.Monitor.ups.AdvOutputLoad | SCUtils.APC.UPS | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.GreaterThanThresholdProbe | True | Public | |
| UPS Basic Battery Status |
Healthy if equal to 2. Monitor warning indicates that the battery status is either 'Unknown' (communication with the UPS has been lost) or that the battery is running low and will turn off shortly. This is used as a final warning condition.
| SCUtils.APC.UPS.Monitor.ups.BasicBatteryStatus | SCUtils.APC.UPS | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Error | Normal | True | SCUtils.APC.UPS.Monitor.Type.StatusProbe | True | Public | |
| UPS Basic Output Status |
Healthy if equal to 2. Monitor warning indicates that the UPS is running on battery (3) or is not providing line voltage to any attached devices.
| SCUtils.APC.UPS.Monitor.ups.BasicOutputStatus | SCUtils.APC.UPS | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | Warning | Normal | True | SCUtils.APC.UPS.Monitor.Type.StatusProbe | True | Public | |