UPS Battery Temperature

SCUtils.APC.UPS.Monitor.ups.AdvBatteryTemperature (UnitMonitor)

Element properties:

TargetSCUtils.APC.UPS
Parent MonitorSystem.Health.AvailabilityState
CategoryAvailabilityHealth
EnabledTrue
Alert GenerateTrue
Alert SeverityWarning
Alert PriorityNormal
Alert Auto ResolveTrue
Monitor TypeSCUtils.APC.UPS.Monitor.Type.GreaterThanThresholdProbe
RemotableTrue
AccessibilityPublic
Alert Message
Battery Temperature

Battery Temperature {4}

Sourse: {0}
Location: {1}
Primary Owner: {2}
IP : {3}

Healthy if less than 45.
The current internal UPS temperature expressed in Celsius.
RunAsDefault

Source Code:

<UnitMonitor ID="SCUtils.APC.UPS.Monitor.ups.AdvBatteryTemperature" Accessibility="Public" Enabled="true" Target="SCUtils.APC.UPS" ParentMonitorID="Health!System.Health.AvailabilityState" Remotable="true" Priority="Normal" TypeID="SCUtils.APC.UPS.Monitor.Type.GreaterThanThresholdProbe" ConfirmDelivery="true">
<Category>AvailabilityHealth</Category>
<AlertSettings AlertMessage="SCUtils.APC.UPS.Monitor.ups.AdvBatteryTemperature_AlertMessageResourceID">
<AlertOnState>Warning</AlertOnState>
<AutoResolve>true</AutoResolve>
<AlertPriority>Normal</AlertPriority>
<AlertSeverity>Warning</AlertSeverity>
<AlertParameters>
<AlertParameter1>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/sysName$</AlertParameter1>
<AlertParameter2>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/Location$</AlertParameter2>
<AlertParameter3>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/PrimaryOwnerContact$</AlertParameter3>
<AlertParameter4>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPAddress$</AlertParameter4>
<AlertParameter5>$Data/Context/SnmpVarBinds/SnmpVarBind[1]/Value$</AlertParameter5>
</AlertParameters>
</AlertSettings>
<OperationalStates>
<OperationalState ID="SCUtils.APC.UPS.Monitor.ups.AdvBatteryTemperature.Success" MonitorTypeStateID="StatusOK" HealthState="Success"/>
<OperationalState ID="SCUtils.APC.UPS.Monitor.ups.AdvBatteryTemperature.Error" MonitorTypeStateID="StatusNotOK" HealthState="Warning"/>
</OperationalStates>
<Configuration>
<IntervalSeconds>600</IntervalSeconds>
<IPAddress>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPAddress$</IPAddress>
<CommunityString>$RunAs[Name="NetworkLibrary!System.NetworkManagement.Snmp.MonitoringAccount"]/CommunityString$</CommunityString>
<SnmpVersion>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPVersion$</SnmpVersion>
<OID>.1.3.6.1.4.1.318.1.1.1.2.2.2.0</OID>
<Threshold>45</Threshold>
</Configuration>
</UnitMonitor>