UPS Output Voltage
SCUtils.APC.UPS.Rule.ups.AdvOutputVoltage (Rule)
The output voltage of the UPS system in VAC.
Element properties:
Member Modules:
Source Code:
<Rule ID="SCUtils.APC.UPS.Rule.ups.AdvOutputVoltage" Enabled="true" Target="SCUtils.APC.UPS" ConfirmDelivery="false" Remotable="true" Priority="Normal" DiscardLevel="100">
<Category>PerformanceCollection</Category>
<DataSources>
<DataSource ID="DS" TypeID="NetworkLibrary!System.NetworkManagement.SnmpPerformanceDataSource">
<Interval>300</Interval>
<NoOfRetries>3</NoOfRetries>
<Timeout>500</Timeout>
<Port>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/PortNumber$</Port>
<IP>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPAddress$</IP>
<Version>$Target/Property[Type="NetworkLibrary!System.NetworkManagement.Node"]/SNMPVersion$</Version>
<SnmpVarBinds>
<SnmpVarBind>
<OID>.1.3.6.1.4.1.318.1.1.1.4.2.1.0</OID>
<Syntax>0</Syntax>
<Value VariantType="8"/>
</SnmpVarBind>
</SnmpVarBinds>
<ObjectName>Output Voltage</ObjectName>
<CounterName>In VAC</CounterName>
</DataSource>
</DataSources>
<WriteActions>
<WriteAction ID="CollectToDB" TypeID="SC!Microsoft.SystemCenter.CollectPerformanceData"/>
<WriteAction ID="CollectToDW" TypeID="SCDW!Microsoft.SystemCenter.DataWarehouse.PublishPerformanceData"/>
</WriteActions>
</Rule>