| DisplayName | Description | ID | Target | Parent Monitor | Category | Enabled | Instance Name | Counter Name | Frequency | Alert Generate | Alert Severity | Alert Priority | Alert Auto Resolve | Monitor Type | Remotable | Accessibility | RunAs |
| PDU Phase/Bank State |
Getting this OID will return the phase/bank load state.
phaseLoadNormal(1) indicates that the phase/bank is
operating properly within the rPDULoadConfigLowLoadThreshold
and rPDULoadConfigNearOverloadThreshold OID values.
phaseLoadLow(2) indicates that the phase/bank load has
dropped below the rPDULoadConfigLowLoadThreshold OID value.
An SNMP trap will occur when this state is entered or cleared.
phaseLoadNearOverload(3) indicates that the phase/bank load
is greater than or equal to the
rPDULoadConfigNearOverloadThreshold OID value.
An SNMP trap will occur when this state is entered or cleared.
phaseLoadOverload(4) indicates that the phase/bank load is
greater than or equal to the rPDULoadConfigOverloadThreshold
OID value.
An SNMP trap will occur when this state is entered or cleared.
| SCUtils.APC.PDU.Monitor.rPDULoadStatusLoadState | SCUtils.APC.PDU.PhaseBank | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.ThreeLevel.StatusProbe | True | Public | |
| PDU Power Supply Alarm | Getting this OID will return powerSupply Alarm | SCUtils.APC.PDU.Monitor.rPDUPowerSupplyAlarm | SCUtils.APC.PDU | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.StatusProbe | True | Public | |
| Phase Load Status | Indicates the present load status of the Rack PDU phase being queried | SCUtils.APC.PDU2.Bank.Monitor.rPDU2BankStatusLoadState | SCUtils.APC.PDU2.Bank | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.ThreeLevel.StatusProbe | True | Public | |
| PDU Load Status |
Indicates the present load status of the Rack PDU
| SCUtils.APC.PDU2.Device.Monitor.rPDU2DeviceStatusLoadState | SCUtils.APC.PDU2.Device | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.ThreeLevel.StatusProbe | True | Public | |
| PDU Power Supply 1 Alarm | Getting this OID will return power supply 1 Alarm | SCUtils.APC.PDU2.Device.Monitor.rPDU2DeviceStatusPowerSupply1Status | SCUtils.APC.PDU2.Device | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.StatusProbe | True | Public | |
| PDU Power Supply 2 Alarm | Getting this OID will return power supply 2 Alarm | SCUtils.APC.PDU2.Device.Monitor.rPDU2DeviceStatusPowerSupply2Status | SCUtils.APC.PDU2.Device | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.StatusProbe | True | Public | |
| Phase Load Status | Indicates the present load status of the Rack PDU phase being queried | SCUtils.APC.PDU2.OutletMetered.Monitor.rPDU2OutletMeteredStatusState | SCUtils.APC.PDU2.OutletMetered | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.ThreeLevel.StatusProbe | True | Public | |
| Bank Load Status | Indicates the present load status of the Rack PDU bank being queried | SCUtils.APC.PDU2.Phase.Monitor.rPDU2PhaseStatusLoadState | SCUtils.APC.PDU2.Phase | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.ThreeLevel.StatusProbe | True | Public | |
| Sensor Communication Status | The communications status of the sensor | SCUtils.APC.PDU2.Sensor.Monitor.rPDU2SensorTempHumidityStatusCommStatus | SCUtils.APC.PDU2.Sensor | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.StatusProbe | True | Public | |
| Humidity Status |
This OID reports the current state of the humidity probe.
A notPresent (1) response indicates that no probe is attached.
A belowMin (2) response indicates that the probe is present and its measured humidity lies below the minimum threshold.
A belowLow (3) response indicates that the probe is present and its measured humidity lies below the low threshold.
A normal (4) response indicates that the probe is present and its measured humidity lies within all humidity thresholds.
An aboveHigh (5) response indicates that the probe is present and is measuring a humidity above the high threshold.
An aboveMax (6) response indicates that the probe is present and is measuring a humidity above the max threshold.
| SCUtils.APC.PDU2.Sensor.Monitor.rPDU2SensorTempHumidityStatusHumidityStatus | SCUtils.APC.PDU2.Sensor | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.ThreeLevel.StatusProbe | True | Public | |
| Temperature Status |
This OID reports the current state of the temperature probe.
A notPresent (1) response indicates that no probe is attached.
A belowMin (2) response indicates that the probe is present and
its measured temperature lies below the minimum threshold.
A belowLow (3) response indicates that the probe is present and
its measured temperature lies below the low threshold.
A normal (4) response indicates that the probe is present
and its measured temperature lies within all temperature thresholds.
An aboveHigh (5) response indicates that the probe is present
and is measuring a temperature above the high threshold.
An aboveMax (6) response indicates that the probe is present
and is measuring a temperature above the max threshold.
| SCUtils.APC.PDU2.Sensor.Monitor.rPDU2SensorTempHumidityStatusTempStatus | SCUtils.APC.PDU2.Sensor | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.ThreeLevel.StatusProbe | True | Public | |
| Discrete Sensor Alarm Status | Indicates alarm status of discrete sensor input | SCUtils.APC.PDU2.SensorDiscrete.Monitor.rPDU2SensorDiscreteStatusAlarmState | SCUtils.APC.PDU2.SensorDiscrete | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.StatusProbe | True | Public | |
| Discrete Sensor Communication Status | The communications status of the sensor | SCUtils.APC.PDU2.SensorDiscrete.Monitor.rPDU2SensorDiscreteStatusCommStatus | SCUtils.APC.PDU2.SensorDiscrete | System.Health.AvailabilityState | AvailabilityHealth | True | | | 0 | True | MatchMonitorHealth | Normal | True | SCUtils.APC.PDU.MonitorType.StatusProbe | True | Public | |