| DisplayName | ID | Target | Category | Enabled | Alert Generate |
![SCUtils.APC.EMU.Rule.CollectEMUProbeHumidity](/images/Rule.png) | APC EMU Probe Humidity Rule | SCUtils.APC.EMU.Rule.CollectEMUProbeHumidity | SCUtils.APC.EMUProbe | PerformanceCollection | True | False |
![SCUtils.APC.EMU.Rule.CollectEMUProbeTemperature](/images/Rule.png) | APC EMU Probe Temperature Rule | SCUtils.APC.EMU.Rule.CollectEMUProbeTemperature | SCUtils.APC.EMUProbe | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.CollectUPSIEMProbeHumidity](/images/Rule.png) | Environment Humidity | SCUtils.APC.UPS.Rule.CollectUPSIEMProbeHumidity | SCUtils.APC.UPS.IEM.Probe | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.CollectUPSIEMProbeTemp](/images/Rule.png) | Environment temperature | SCUtils.APC.UPS.Rule.CollectUPSIEMProbeTemp | SCUtils.APC.UPS.IEM.Probe | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsAdvBatteryCapacity](/images/Rule.png) | UPS Battery Capacity | SCUtils.APC.UPS.Rule.upsAdvBatteryCapacity | SCUtils.APC.UPS.System | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsAdvBatteryRunTimeRemaining](/images/Rule.png) | UPS Battery RunTime Remaining | SCUtils.APC.UPS.Rule.upsAdvBatteryRunTimeRemaining | SCUtils.APC.UPS.System | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsAdvBatteryTemperature](/images/Rule.png) | UPS Battery Temperature | SCUtils.APC.UPS.Rule.upsAdvBatteryTemperature | SCUtils.APC.UPS.System | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsAdvInputFrequency](/images/Rule.png) | UPS Input Frequency | SCUtils.APC.UPS.Rule.upsAdvInputFrequency | SCUtils.APC.UPS.Device | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsAdvInputLineVoltage](/images/Rule.png) | UPS Input Line Voltage | SCUtils.APC.UPS.Rule.upsAdvInputLineVoltage | SCUtils.APC.UPS.Device | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsAdvOutputCurrent](/images/Rule.png) | UPS Output Current | SCUtils.APC.UPS.Rule.upsAdvOutputCurrent | SCUtils.APC.UPS.Device | PerformanceCollection | False | False |
![SCUtils.APC.UPS.Rule.upsAdvOutputFrequency](/images/Rule.png) | UPS Output Frequency | SCUtils.APC.UPS.Rule.upsAdvOutputFrequency | SCUtils.APC.UPS.Device | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsAdvOutputLoad](/images/Rule.png) | UPS Output Load | SCUtils.APC.UPS.Rule.upsAdvOutputLoad | SCUtils.APC.UPS.Device | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsAdvOutputVoltage](/images/Rule.png) | UPS Output Voltage | SCUtils.APC.UPS.Rule.upsAdvOutputVoltage | SCUtils.APC.UPS.Device | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsBasicBattery.TimeOnBattery](/images/Rule.png) | UPS Time On Battery | SCUtils.APC.UPS.Rule.upsBasicBattery.TimeOnBattery | SCUtils.APC.UPS.System | PerformanceCollection | True | False |
![SCUtils.APC.UPS.Rule.upsBasicBatteryStatus](/images/Rule.png) | UPS Basic Battery Status | SCUtils.APC.UPS.Rule.upsBasicBatteryStatus | SCUtils.APC.UPS.System | PerformanceCollection | True | False |
![SCUtils.APC.UPS.TrapRule.apcInternalCommunicationFault](/images/Rule.png) | UPS Alert trap Rule - An internal UPS communication fault exists | SCUtils.APC.UPS.TrapRule.apcInternalCommunicationFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.apcInternalCommunicationFaultCleared](/images/Rule.png) | UPS Alert trap Rule - An internal UPS communication fault no longer exists | SCUtils.APC.UPS.TrapRule.apcInternalCommunicationFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.apcTestTrap](/images/Rule.png) | UPS Alert trap Rule - Test SNMP trap | SCUtils.APC.UPS.TrapRule.apcTestTrap | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.badVoltage](/images/Rule.png) | UPS Alert trap Rule - The output voltage is not within acceptable range | SCUtils.APC.UPS.TrapRule.badVoltage | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.badVoltageCleared](/images/Rule.png) | UPS Alert trap Rule - The output voltage has returned to an acceptable level | SCUtils.APC.UPS.TrapRule.badVoltageCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.baseFanFailure](/images/Rule.png) | UPS Alert trap Rule - Base module fan needs repair | SCUtils.APC.UPS.TrapRule.baseFanFailure | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.batteryOverTemperature](/images/Rule.png) | UPS Alert trap Rule - The battery temperature threshold has been violated | SCUtils.APC.UPS.TrapRule.batteryOverTemperature | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.batteryOverTemperatureCleared](/images/Rule.png) | UPS Alert trap Rule - The battery over temperature has been cleared | SCUtils.APC.UPS.TrapRule.batteryOverTemperatureCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.batteryPackCommEstablished](/images/Rule.png) | UPS Alert trap Rule - UPS is communicating with the external battery packs | SCUtils.APC.UPS.TrapRule.batteryPackCommEstablished | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.batteryPackCommLost](/images/Rule.png) | UPS Alert trap Rule - Check installation of external battery packs signal cable | SCUtils.APC.UPS.TrapRule.batteryPackCommLost | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.bypassPowerSupplyFailure](/images/Rule.png) | UPS Alert trap Rule - Base module bypass power supply needs repair | SCUtils.APC.UPS.TrapRule.bypassPowerSupplyFailure | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.calibrationEnd](/images/Rule.png) | UPS Alert trap Rule - The UPS has finished calibrating | SCUtils.APC.UPS.TrapRule.calibrationEnd | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.calibrationStart](/images/Rule.png) | UPS Alert trap Rule - A battery calibration test has been initiated on the UPS | SCUtils.APC.UPS.TrapRule.calibrationStart | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.chargerFailure](/images/Rule.png) | UPS Alert trap Rule - The battery charger has failed | SCUtils.APC.UPS.TrapRule.chargerFailure | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.chargerFailureCleared](/images/Rule.png) | UPS Alert trap Rule - The battery charger failure condition has been cleared | SCUtils.APC.UPS.TrapRule.chargerFailureCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.codeAuthenticationDone](/images/Rule.png) | UPS Alert trap Rule - Authentication on agent code image is done | SCUtils.APC.UPS.TrapRule.codeAuthenticationDone | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.communicationEstablished](/images/Rule.png) | UPS Alert trap Rule - Communication with the UPS has been established | SCUtils.APC.UPS.TrapRule.communicationEstablished | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.communicationLost](/images/Rule.png) | UPS Alert trap Rule - Communication to the UPS has been lost | SCUtils.APC.UPS.TrapRule.communicationLost | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.contactFault](/images/Rule.png) | UPS Alert trap Rule - One of the contacts on the Environmental Monitor has changed from its default position | SCUtils.APC.UPS.TrapRule.contactFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.contactFaultResolved](/images/Rule.png) | UPS Alert trap Rule - A fault on one of the Environmental Monitor contacts has been resolved | SCUtils.APC.UPS.TrapRule.contactFaultResolved | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.dischargeCleared](/images/Rule.png) | UPS Alert trap Rule - A UPS discharge condition has been cleared | SCUtils.APC.UPS.TrapRule.dischargeCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.gracefulShutdown](/images/Rule.png) | UPS Alert trap Rule - A graceful shutdown has been initiated | SCUtils.APC.UPS.TrapRule.gracefulShutdown | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.hardwareFailureBypass](/images/Rule.png) | UPS Alert trap Rule - UPS on bypass due to internal fault | SCUtils.APC.UPS.TrapRule.hardwareFailureBypass | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.humidityThresholdViolation1](/images/Rule.png) | UPS Alert trap Rule - Probe 1 humidity threshold violated | SCUtils.APC.UPS.TrapRule.humidityThresholdViolation1 | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.humidityThresholdViolation2](/images/Rule.png) | UPS Alert trap Rule - An Environmental Monitor humidity threshold has been violated on probe 2 | SCUtils.APC.UPS.TrapRule.humidityThresholdViolation2 | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.humidityThresholdViolationCleared1](/images/Rule.png) | UPS Alert trap Rule - An Environmental Monitor humidity threshold violation has been cleared on probe 1 | SCUtils.APC.UPS.TrapRule.humidityThresholdViolationCleared1 | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.humidityThresholdViolationCleared2](/images/Rule.png) | UPS Alert trap Rule - An Environmental Monitor humidity threshold violation has been cleared on probe 2 | SCUtils.APC.UPS.TrapRule.humidityThresholdViolationCleared2 | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.lowBattery](/images/Rule.png) | UPS Alert trap Rule - The UPS batteries are low | SCUtils.APC.UPS.TrapRule.lowBattery | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.onbatterycommunicationLost](/images/Rule.png) | UPS Alert trap Rule - Communication to the UPS when the UPS is on Battery | SCUtils.APC.UPS.TrapRule.onbatterycommunicationLost | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.powerRestored](/images/Rule.png) | UPS Alert trap Rule - Utility power has been restored | SCUtils.APC.UPS.TrapRule.powerRestored | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.restartAgent](/images/Rule.png) | UPS Alert trap Rule - Agent restarting as commanded by manager | SCUtils.APC.UPS.TrapRule.restartAgent | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.returnFromBypass](/images/Rule.png) | UPS Alert trap Rule - UPS has returned from bypass | SCUtils.APC.UPS.TrapRule.returnFromBypass | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.returnFromLowBattery](/images/Rule.png) | UPS Alert trap Rule - The UPS has returned from a low battery condition | SCUtils.APC.UPS.TrapRule.returnFromLowBattery | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.smartAvrReducing](/images/Rule.png) | UPS Alert trap Rule - The UPS is reducing the line voltage via SmartTrim(TM) | SCUtils.APC.UPS.TrapRule.smartAvrReducing | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.smartAvrReducingOff](/images/Rule.png) | UPS Alert trap Rule - The UPS has returned from SmartTrim(TM) | SCUtils.APC.UPS.TrapRule.smartAvrReducingOff | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.smartBoostOff](/images/Rule.png) | UPS Alert trap Rule - The UPS has returned from SmartBoost(TM) | SCUtils.APC.UPS.TrapRule.smartBoostOff | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.smartBoostOn](/images/Rule.png) | UPS Alert trap Rule - The UPS has enabled SmartBoost(TM) | SCUtils.APC.UPS.TrapRule.smartBoostOn | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.smartRelayFault](/images/Rule.png) | UPS Alert trap Rule - SmartBoost(TM) or SmartTrim(TM) relay fault | SCUtils.APC.UPS.TrapRule.smartRelayFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.smartRelayFaultCleared](/images/Rule.png) | UPS Alert trap Rule - SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared | SCUtils.APC.UPS.TrapRule.smartRelayFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.softwareBypass](/images/Rule.png) | UPS Alert trap Rule - UPS on bypass - user set | SCUtils.APC.UPS.TrapRule.softwareBypass | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.switchedBypass](/images/Rule.png) | UPS Alert trap Rule - UPS on bypass | SCUtils.APC.UPS.TrapRule.switchedBypass | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.temperatureThresholdViolation1](/images/Rule.png) | UPS Alert trap Rule - An Environmental Monitor temperature threshold has been violated on probe 1 | SCUtils.APC.UPS.TrapRule.temperatureThresholdViolation1 | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.temperatureThresholdViolation2](/images/Rule.png) | UPS Alert trap Rule - An Environmental Monitor temperature threshold has been violated on probe 2 | SCUtils.APC.UPS.TrapRule.temperatureThresholdViolation2 | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.temperatureThresholdViolationCleared1](/images/Rule.png) | UPS Alert trap Rule - An Environmental Monitor temperature threshold violation has been cleared on probe 1 | SCUtils.APC.UPS.TrapRule.temperatureThresholdViolationCleared1 | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.temperatureThresholdViolationCleared2](/images/Rule.png) | UPS Alert trap Rule - An Environmental Monitor temperature threshold violation has been cleared on probe 2 | SCUtils.APC.UPS.TrapRule.temperatureThresholdViolationCleared2 | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBackfeedRelayFault](/images/Rule.png) | UPS Alert trap Rule - The backfeed relay has a fault | SCUtils.APC.UPS.TrapRule.upsBackfeedRelayFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBackfeedRelayFaultCleared](/images/Rule.png) | UPS Alert trap Rule - The backfeed relay has a fault cleared | SCUtils.APC.UPS.TrapRule.upsBackfeedRelayFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBatteryNeedsReplacement](/images/Rule.png) | UPS Alert trap Rule - The batteries of the UPS need immediate replacement | SCUtils.APC.UPS.TrapRule.upsBatteryNeedsReplacement | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBatteryReplaced](/images/Rule.png) | UPS Alert trap Rule - A bad battery fault has been cleared | SCUtils.APC.UPS.TrapRule.upsBatteryReplaced | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBatterySoftBusStartFault](/images/Rule.png) | UPS Alert trap Rule - A battery bus soft start fault exists | SCUtils.APC.UPS.TrapRule.upsBatterySoftBusStartFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBatterySoftBusStartFaultCleared](/images/Rule.png) | UPS Alert trap Rule - A battery bus soft start fault exists cleared | SCUtils.APC.UPS.TrapRule.upsBatterySoftBusStartFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBatteryTempSensorFault](/images/Rule.png) | UPS Alert trap Rule - The battery temperature sensor fault exists | SCUtils.APC.UPS.TrapRule.upsBatteryTempSensorFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBatteryTempSensorFaultCleared](/images/Rule.png) | UPS Alert trap Rule - The battery temperature sensor fault cleared | SCUtils.APC.UPS.TrapRule.upsBatteryTempSensorFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBypassRelayFault](/images/Rule.png) | UPS Alert trap Rule - A bypass relay has a fault | SCUtils.APC.UPS.TrapRule.upsBypassRelayFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsBypassRelayFaultCleared](/images/Rule.png) | UPS Alert trap Rule - A bypass relay has a fault cleared | SCUtils.APC.UPS.TrapRule.upsBypassRelayFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsCalibrationStackChanged](/images/Rule.png) | UPS Alert trap Rule - A calibration value in the stack was changed | SCUtils.APC.UPS.TrapRule.upsCalibrationStackChanged | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsCriticalCondition](/images/Rule.png) | UPS Alert trap Rule - A UPS critical condition was detected | SCUtils.APC.UPS.TrapRule.upsCriticalCondition | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsCriticalConditionCleared](/images/Rule.png) | UPS Alert trap Rule - A UPS critical condition has been cleared | SCUtils.APC.UPS.TrapRule.upsCriticalConditionCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsDiagnosticsFailed](/images/Rule.png) | UPS Alert trap Rule - The UPS failed its internal diagnostic self-test | SCUtils.APC.UPS.TrapRule.upsDiagnosticsFailed | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsDiagnosticsPassed](/images/Rule.png) | UPS Alert trap Rule - The UPS passed its internal self-test | SCUtils.APC.UPS.TrapRule.upsDiagnosticsPassed | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsDipSwitchChanged](/images/Rule.png) | UPS Alert trap Rule - The dip switch settings on the UPS have been changed | SCUtils.APC.UPS.TrapRule.upsDipSwitchChanged | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsDischarged](/images/Rule.png) | UPS Alert trap Rule - The UPS batteries are discharged | SCUtils.APC.UPS.TrapRule.upsDischarged | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsEPOActive](/images/Rule.png) | UPS Alert trap Rule - Emergency Power Off (EPO) active | SCUtils.APC.UPS.TrapRule.upsEPOActive | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsEPOActiveCleared](/images/Rule.png) | UPS Alert trap Rule - Emergency Power Off (EPO) now inactive | SCUtils.APC.UPS.TrapRule.upsEPOActiveCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsFirmwareMismatch](/images/Rule.png) | UPS Alert trap Rule - A firmware mismatch error exists | SCUtils.APC.UPS.TrapRule.upsFirmwareMismatch | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsFirmwareMismatchCleared](/images/Rule.png) | UPS Alert trap Rule - A firmware mismatch error no longer exists | SCUtils.APC.UPS.TrapRule.upsFirmwareMismatchCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsFirmwareUpdateFailed](/images/Rule.png) | UPS Alert trap Rule - UPS firmware update failed | SCUtils.APC.UPS.TrapRule.upsFirmwareUpdateFailed | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsFirmwareUpdateFinished](/images/Rule.png) | UPS Alert trap Rule - Finished updating UPS firmware | SCUtils.APC.UPS.TrapRule.upsFirmwareUpdateFinished | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsFirmwareUpdateStarted](/images/Rule.png) | UPS Alert trap Rule - Updating UPS firmware | SCUtils.APC.UPS.TrapRule.upsFirmwareUpdateStarted | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsFirmwareUpdateSucceeded](/images/Rule.png) | UPS Alert trap Rule - UPS firmware update succeeded | SCUtils.APC.UPS.TrapRule.upsFirmwareUpdateSucceeded | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsHasNoValidFirmware](/images/Rule.png) | UPS Alert trap Rule - UPS has no valid firmware | SCUtils.APC.UPS.TrapRule.upsHasNoValidFirmware | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsHasNoValidFirmwareCleared](/images/Rule.png) | UPS Alert trap Rule - UPS now has a valid firmware | SCUtils.APC.UPS.TrapRule.upsHasNoValidFirmwareCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsInformationalCondition](/images/Rule.png) | UPS Alert trap Rule - A UPS informational condition has been detected | SCUtils.APC.UPS.TrapRule.upsInformationalCondition | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsInformationalConditionCleared](/images/Rule.png) | UPS Alert trap Rule - A UPS informational condition has been cleared | SCUtils.APC.UPS.TrapRule.upsInformationalConditionCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsInternalOverTemperature](/images/Rule.png) | UPS Alert trap Rule - The internal over temperature condition exists | SCUtils.APC.UPS.TrapRule.upsInternalOverTemperature | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsInternalOverTemperatureCleared](/images/Rule.png) | UPS Alert trap Rule - The internal over temperature condition cleared | SCUtils.APC.UPS.TrapRule.upsInternalOverTemperatureCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsInverterFault](/images/Rule.png) | UPS Alert trap Rule - The inverter fault exists | SCUtils.APC.UPS.TrapRule.upsInverterFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsInverterFaultCleared](/images/Rule.png) | UPS Alert trap Rule - The inverter fault cleared | SCUtils.APC.UPS.TrapRule.upsInverterFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsLocalDisplayButtonFault](/images/Rule.png) | UPS Alert trap Rule - A local display button fault exists | SCUtils.APC.UPS.TrapRule.upsLocalDisplayButtonFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsLocalDisplayButtonFaultCleared](/images/Rule.png) | UPS Alert trap Rule - A local display button fault no longer exists | SCUtils.APC.UPS.TrapRule.upsLocalDisplayButtonFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsMpuReset](/images/Rule.png) | UPS Alert trap Rule - The MPU has been reset | SCUtils.APC.UPS.TrapRule.upsMpuReset | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsNeedsFactorySetupFault](/images/Rule.png) | UPS Alert trap Rule - UPS needs factory setup | SCUtils.APC.UPS.TrapRule.upsNeedsFactorySetupFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsNeedsFactorySetupFaultCleared](/images/Rule.png) | UPS Alert trap Rule - UPS no longer needs factory setup | SCUtils.APC.UPS.TrapRule.upsNeedsFactorySetupFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOnBattery](/images/Rule.png) | UPS Alert trap Rule - The UPS has switched to battery backup power | SCUtils.APC.UPS.TrapRule.upsOnBattery | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOnBatteryDueToFault](/images/Rule.png) |
UPS Alert trap Rule - The UPS is on battery due to an error.
| SCUtils.APC.UPS.TrapRule.upsOnBatteryDueToFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOnBatteryDueToFaultCleared](/images/Rule.png) | UPS Alert trap Rule - The UPS is no longer on battery due to an error | SCUtils.APC.UPS.TrapRule.upsOnBatteryDueToFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOscillatorFailed](/images/Rule.png) | UPS Alert trap Rule - An oscillator error exists | SCUtils.APC.UPS.TrapRule.upsOscillatorFailed | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOscillatorFailedCleared](/images/Rule.png) | UPS Alert trap Rule - An oscillator error no longer exists | SCUtils.APC.UPS.TrapRule.upsOscillatorFailedCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOutletGroupCommand](/images/Rule.png) | UPS Alert trap Rule - The specified Outlet Group command has been issued | SCUtils.APC.UPS.TrapRule.upsOutletGroupCommand | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOutletGroupTurnedOff](/images/Rule.png) | UPS Alert trap Rule - The specified Outlet Group turned off | SCUtils.APC.UPS.TrapRule.upsOutletGroupTurnedOff | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOutletGroupTurnedOn](/images/Rule.png) | UPS Alert trap Rule - The specified Outlet Group turned on | SCUtils.APC.UPS.TrapRule.upsOutletGroupTurnedOn | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOutputSwitchClosed](/images/Rule.png) | UPS Alert trap Rule - The Output Switch is closed | SCUtils.APC.UPS.TrapRule.upsOutputSwitchClosed | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOutputSwitchOpened](/images/Rule.png) | UPS Alert trap Rule - The Output Switch is open | SCUtils.APC.UPS.TrapRule.upsOutputSwitchOpened | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOverload](/images/Rule.png) | UPS Alert trap Rule - The UPS overload | SCUtils.APC.UPS.TrapRule.upsOverload | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsOverloadCleared](/images/Rule.png) | UPS Alert trap Rule - The overload condition has been cleared | SCUtils.APC.UPS.TrapRule.upsOverloadCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsPfcFault](/images/Rule.png) | UPS Alert trap Rule - A PFC fault exists | SCUtils.APC.UPS.TrapRule.upsPfcFault | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsPfcFaultCleared](/images/Rule.png) | UPS Alert trap Rule - The PFC fault cleared | SCUtils.APC.UPS.TrapRule.upsPfcFaultCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsRebootStarted](/images/Rule.png) | UPS Alert trap Rule - The UPS has started its reboot sequence | SCUtils.APC.UPS.TrapRule.upsRebootStarted | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsSleeping](/images/Rule.png) | UPS Alert trap Rule - The UPS is entering 'sleep' mode | SCUtils.APC.UPS.TrapRule.upsSleeping | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsTurnedOff](/images/Rule.png) | UPS Alert trap Rule - The UPS has been turned 'off' | SCUtils.APC.UPS.TrapRule.upsTurnedOff | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsTurnedOn](/images/Rule.png) | UPS Alert trap Rule - A UPS is turned on | SCUtils.APC.UPS.TrapRule.upsTurnedOn | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsWarningCondition](/images/Rule.png) | UPS Alert trap Rule - A UPS warning condition has been detected | SCUtils.APC.UPS.TrapRule.upsWarningCondition | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsWarningConditionCleared](/images/Rule.png) | UPS Alert trap Rule - A UPS warning condition has been cleared | SCUtils.APC.UPS.TrapRule.upsWarningConditionCleared | SCUtils.APC.UPS.Device | Alert | True | True |
![SCUtils.APC.UPS.TrapRule.upsWokeUp](/images/Rule.png) | UPS Alert trap Rule - The UPS has returned from 'sleep' mode | SCUtils.APC.UPS.TrapRule.upsWokeUp | SCUtils.APC.UPS.Device | Alert | True | True |